Buy Xtreme Power Conversion XPRT-6000HB 90000036 6kVA/4.2kW 208V 4U UPS w/Maintenance Bypass in United States - Cartnear.com

Xtreme Power Conversion XPRT-6000HB 90000036 6kVA/4.2kW 208V 4U UPS w/Maintenance Bypass

CTNR1284268 CTNR1284268

Xtreme Power Conversion

Xtreme Power Conversion
2025-11-22 USD 5642.25

$ 5,642.25 $ 5,757.40

Item Added to Cart

*Product availability is subject to suppliers inventory

Xtreme Power Conversion XPRT-6000HB 90000036 6kVA/4.2kW 208V 4U UPS w/Maintenance Bypass
SHIPPING ALL OVER UNITED STATES
Xtreme Power Conversion XPRT-6000HB 90000036 6kVA/4.2kW 208V 4U UPS w/Maintenance Bypass
100% MONEY BACK GUARANTEE
Xtreme Power Conversion XPRT-6000HB 90000036 6kVA/4.2kW 208V 4U UPS w/Maintenance Bypass
EASY 30 DAYSRETURNS & REFUNDS
Xtreme Power Conversion XPRT-6000HB 90000036 6kVA/4.2kW 208V 4U UPS w/Maintenance Bypass
24/7 CUSTOMER SUPPORT
Xtreme Power Conversion XPRT-6000HB 90000036 6kVA/4.2kW 208V 4U UPS w/Maintenance Bypass
TRUSTED AND SAFE WEBSITE
Xtreme Power Conversion XPRT-6000HB 90000036 6kVA/4.2kW 208V 4U UPS w/Maintenance Bypass
100% SECURE CHECKOUT
Brand Xtreme Power Conversion
Series XPRT Series
Model XPRT-6000HB
Input Voltage Range 100/(173-200), 110/(190-220), 115/(198-230), 120/(208-240), 127/(220)VAC*
Input Frequency 40–70Hz
Input Connection Hardwire
VA Rating 6kVA
Watts 4.2kW
Output Voltage 208/120VAC, 240/120VAC auto-sensing; 230/115VAC, 200/100VAC selectable
Output Frequency 50/60Hz auto-sensing ± 5% or frequency converter
Outlets Hardwire
Outlet Type Hardwire
Battery Recharge Time < 3 hours to 90%
Battery Replaceable Hot swappable internal batteries
Approvals UL, cUL, FCC
Rackmountable Yes
Dimensions 16.9 x 22.5 x 6.9 in
Weight 162 lbs
These true online, double conversion UPS systems provide more capacity in less space. The XPRT-6kVA (4U) and XPRT-10kVA (6U) models save space, weight, and power through a dual inverter design which provides selectable output voltages of 208/120V, 240/120V, 230/115V, or 200/100V without the need for transformers. The XPRT-10kVA features hardwired input and output terminals and an optional output receptacle module. It includes one internal power module and two internal battery modules. The chassis contains a bypass switch which allows all modules to be removed without powering down the connected load.